Skip to main content Skip to search Skip to navigation
You are in the private customer shopOver 20 years of experience – since 2001Personal advice: +49 931 40453960Tiered prices for resellers on requestFor private customersAll prices incl. VATFor business customersAll prices excl. VAT

Case study: well remediation in Lower Bavaria with DESINFECT WATERCLEAN

News

From practice: well remediation in Lower Bavaria

Initial situation

A water cooperative in Lower Bavaria supplies 6 properties from its own well. The drinking water analysis in June 2016 detected enterococci (22 CFU/100 ml) and coliform bacteria (29 CFU/100 ml) – the limit value under the German Drinking Water Ordinance is 0 CFU/100 ml for both parameters.

Measure

The system was then shock-chlorinated with DESINFECT WATERCLEAN (1.0 %, equivalent to approx. 10 mg/l active chlorine).

Result

In the follow-up analysis by an accredited laboratory (test report December 2016), E. coli, coliform bacteria and enterococci were each at 0 CFU/100 ml.

Microbiological values compared

Parameter Limit value (German Drinking Water Ordinance) Before (June 2016) After (December 2016)
Enterococci 0 CFU/100 ml 22 CFU/100 ml 0 CFU/100 ml
Coliform bacteria 0 CFU/100 ml 29 CFU/100 ml 0 CFU/100 ml
E. coli 0 CFU/100 ml 0 CFU/100 ml 0 CFU/100 ml

Sources: AGROLAB test report (sampling 15.06.2016) and SYNLAB Umweltinstitut test report (sampling 28.11.2016); both laboratories DAkkS-accredited.

Product used: DESINFECT WATERCLEAN · active chlorine from hypochlorous acid, 0.1 % · BAuA reg. no. N-105775

Download the case study as PDF

Individual case from practice – the result depends on the condition of the respective system.

We will be happy to advise you on the disinfection of well and drinking water systems: phone +49 (0)172 6988766 · info@zimmer-reinigungstechnik.de

Use biocides safely. Always read the label and product information before use.